| Abstract -We investigated a small isolated hybrid | | | | accelerates when the input power is higher than |
| power system that used two types of power | | | | the electrical output power of the generator |
| generation; wind turbine and diesel generation. The | | | | (including losses). |
| interaction of diesel generation, the wind turbine, | | | | The diesel decelerates when the input power is |
| and the local load is complicated because both the | | | | lower than the electrical output power of the |
| load and the wind turbine fluctuate during the day. | | | | generator (including losses). An oversized diesel |
| These fluctuations create imbalances in power | | | | engine does not have problems accelerating or |
| distribution (energy sources are not equal to | | | | decelerating, but an undersized diesel engine may |
| energy sinks) that can affect the frequency and | | | | create problems, during, for example, the start-up |
| the voltage in the power system. The addition of | | | | of a wind turbine or large compressor. Figure 5 |
| energy storage will help balance the distribution of | | | | illustrates a condition where the diesel is |
| power in the power network. For this paper, we | | | | undersized with respect to the load. The genset |
| studied the interaction among hybrid power | | | | frequency and the terminal voltage of the wind |
| system components and the relative size of the | | | | turbine generator are shown on the top graph, |
| components. We also show how the contribution | | | | and the real power of the diesel, wind turbine, |
| of wind energy affects the entire power system | | | | water pump, and local load are shown on the |
| and distribution and the role of energy storage | | | | bottom graph. At start-up, the wind turbine uses |
| under the transient conditions caused by load | | | | the smaller, 40-kW generator to motor up and |
| changes and wind turbine startups. | | | | bring the induction machine up to speed. Because |
| Index Terms - wind turbine, diesel generator, | | | | the wind speed is low, the wind turbine operates |
| hybrid power system, renewable energy, energy | | | | at low output power, and the local load is set to |
| storage. | | | | 200 kW. The diesel engine has a rated power of |
| Â | | | | 400 kW. At t = 2 s, the wind turbine is turned on. |
| I. INTRODUCTION | | | | As we can see, the voltage dip and the |
| Windmills were used to pump water and mill grain, | | | | frequency dip are not very large, because the |
| along with many other uses [1, 2, 3, 4]. | | | | wind turbine is started using a smaller generator |
| Today, wind turbines are used for similar | | | | Â |
| purposes (i.e., water or oil pumping, battery | | | | Figure 5. Voltage, frequency, and power to |
| charging, and utility generation). One important | | | | illustratean undersized diesel genset |
| aspect of wind turbine applications, especially in an | | | | At t = 10 s, the 80-kW water pump is started up. |
| industrial environment, is that wind turbines | | | | The startup time for the water pump is longer |
| generate electricity without creating pollution. Wind | | | | than that of the wind turbine because the wind |
| turbines are also well suited for generating | | | | turbine is started when the rotor speed is close |
| electricity in isolated places with no connections to | | | | to the synchronous speed and the wind turbine |
| the utility grid [2,3,4]. However, in isolated | | | | also gets some help from the wind. The voltage |
| applications, especially very small applications, the | | | | drop is not very significant, but the frequency of |
| power system components (sources and loads) | | | | the diesel drops about 3%. The diesel output |
| are limited, and the system networks are weak in | | | | power increases to cover the real power needed, |
| many cases. Thus, any changes in the power | | | | whereas the contribution from the wind turbine is |
| input or output of one component may affect the | | | | insignificant because the wind is low. For a short |
| rest of the system more dramatically than in a | | | | time, the induction generator enters the motoring |
| larger system where the smoothing effect of | | | | range between t = 10.8 s and t = 11.3 s. After |
| many components benefits the overall system. In | | | | the condition is restored, at t = 14 s, the |
| this paper, we analyze a hybrid power system | | | | additional local load (300 kW noncritical) is turned |
| consisting of a wind turbine, a diesel generator, a | | | | on, bringing the total load to 580 kW. Because the |
| local load, and energy storage. We also present | | | | diesel can carry only up to 400 kW and the wind's |
| the impact of energy storage on the power | | | | contribution is very small at about 40 kW, the |
| system performance. The results and conclusions | | | | voltage and frequency start decreasing, and the |
| of this analysis apply to similar hybrid power | | | | voltage and frequency sensors detect the change. |
| systems. | | | | If the frequency drops below 95% and the |
| Â | | | | voltage drops below 90% for an elapsed time of |
| Â | | | | 0.5 s, the controller will drop the additional load |
| Â | | | | (300 kW) and keep the critical load (200 kW) to |
| II. SYSTEM CONFIGURATION | | | | regain the voltage and frequency. After the load |
| The system has two types of generation: the | | | | is shed at t = 14.5 s, the frequency and voltage |
| diesel generator and the wind turbine generator | | | | eventually return to normal. When the frequency |
| (Figure 1). Theenergy storage can act as a load or | | | | drops, the wind turbine's power contribution |
| as a generator depending on the need. The diesel | | | | suddenly jumps because of a sudden increase of |
| generator provides smooth output power, | | | | generating slip. Eventually, the genset frequency |
| whereas the output power of a wind turbine | | | | increases again for a short period and the |
| depends on the wind velocity. As the wind | | | | induction generator enters into the motoring |
| velocity varies, so does is the power generation. | | | | condition (between t = 14.5 s and t = 15 s). This |
| For example, if the wind speed changes very | | | | condition worsens if the mechanical time constant |
| smoothly, the output power of the wind turbine | | | | of the wind turbine rotor (including the blade) is |
| will also change very smoothly. On the other hand, | | | | higher than the diesel genset time constant. In |
| wind turbulence causes the output power to | | | | other words, the changing of the genset rotor |
| fluctuate. Figure 1 is a single line diagram that | | | | speed is much faster than the changing of the |
| represents the analyzed power system. The wind | | | | wind turbine rotor speed. The response to the |
| turbine has an induction generator with a capacity | | | | load change is shown by how fast the governor |
| ranging from 40 kW to 225 kW. At low wind | | | | corrects the frequency and how fast the |
| speeds, the generator operates at 900 rpm with | | | | generator's field excitation control reacts to the |
| a rated capacity of 40 kW. At high wind speeds, | | | | voltage changes. Undersized diesel engine with |
| the generator speed is 1,200 rpm with a rated | | | | energy storage: As shown in the previous |
| capacity of 225 kW. We used 150 kW of energy | | | | subsection, an undersized diesel engine cannot |
| storage as a buffer to operate as a load or a | | | | supply all energy needed, and it must shed some |
| source depending on the need. This paper | | | | of the non-critical load to retain power-system |
| discusses only fixed-speed wind turbine generation | | | | stability. To remedy this situation, a 150-kW |
| and does not cover variable-speed wind turbine | | | | energy storage is installed to bring the combined |
| generation [5]. The diesel engine, which has a | | | | output of the diesel genset and energy storage |
| rated capacity of 400 kW, is operated in parallel | | | | up to 550 kW. Figure 6 shows the improved |
| with the wind turbine to supply the load. The local | | | | power system after the energy storage is added. |
| loads are mostly residential and light loads. Other | | | | The same simulation is performed except it is |
| loads include water pumps, compressors, and | | | | now equipped with an energy storage. There is a |
| heavy equipment. An 80-kW water pump | | | | significant improvement in the frequency |
| represents the transient condition of a heavy load. | | | | regulation after the storage is installed to stabilize |
| Â | | | | the system. The non-critical load (300 kW) |
| Fig 1. One line diagram of power system | | | | survives even during low wind conditions. The |
| Â | | | | frequency dips during the wind turbine start-up |
| Â | | | | and the water pump start-up, and when the 300 |
| III. COMPONENTS OF POWER SYSTEM | | | | kW load non-critical load is switched, it is reduced |
| The system we discuss in this paper consists of | | | | dramatically. Obviously, the capability of the |
| four major subsystems: a diesel generator, a wind | | | | energy storage to deliver a large amount of |
| turbine generator, heavy (industrial) loads, and | | | | power instantaneously plays a major role in |
| energy storage. In the power system network, | | | | restoring the frequency of the power system. An |
| the balance of active power and reactive power | | | | additional benefit is noticed in the system voltage |
| must be maintained. The diesel-genset, then, must | | | | behavior of the wind turbine. Because the change |
| be able to keep the power balanced when the | | | | in the frequency deviation presented to the wind |
| wind turbine or local load varies. This task is easy | | | | turbine induction generator is small and smooth, |
| to accomplish provided the diesel genset is | | | | the behavior of the stator current at the induction |
| sufficiently sized. Although they are important, we | | | | generator is also smooth. Thus it reduces the Ldi |
| will not cover the details of the dynamic model | | | | dt and overall voltage drop across the line. |
| for electric machines used in the simulation. Many | | | | Oversized wind turbine: |
| good textbooks are available on this subject. | | | | When the wind power output exceeds the power |
| A. Diesel Generator | | | | required by the load, the synchronous generator |
| In terms of an electrical system, a diesel | | | | of the diesel genset becomes a synchronous |
| generator can be represented as a prime mover | | | | motor that tends to accelerate the rotor speed |
| and a generator. Ideally, the prime mover is | | | | of the diesel engine. The excess energy from the |
| capable of supplying any power demand up to | | | | wind power, then, tries to drive the diesel engine. |
| rated power at constant frequency, and the | | | | Because the diesel engine has only a small braking |
| synchronous generator connected to it must be | | | | capability resulting from engine compression, the |
| able to keep the voltage constant at any load | | | | frequency control can be lost when the extra |
| condition. Figure 2 is a block diagram of the diesel | | | | power generated by the wind turbine is |
| generator. The diesel engine keeps the frequency | | | | sufficiently high. |
| constant by maintaining the rotor speed constant | | | | Â |
| via its governor. The synchronous generator must | | | | Figure 6. Voltage, frequency, and power to |
| control its output voltage by controlling the | | | | illustratean undersized diesel genset with storage |
| excitation current. Thus, as a unit, the diesel | | | | In Figure 7, the diesel generator has a rated |
| generating system must be able to control its | | | | power of 400 kW, the local load is initially set to |
| frequency and its output voltage. The inertia of | | | | 280 kW and at t = 4 s, and the local load is set |
| the diesel genset, the sensitivity of the governor, | | | | to 100 kW. When the diesel is started, there is |
| and the power capability of the diesel engine all | | | | only a local load of 280 kW. The wind turbine is |
| affect the diesel generator's ability to respond to | | | | then started at t = 2 s with a 225-kW induction |
| frequency changes. The ability of the synchronous | | | | machine. Although the diesel genset is rated at |
| generator to control its voltage is affected by the | | | | only 400 kW and the wind turbine is started with |
| field winding time constant, the availability of the | | | | a 225-kW induction machine, the effect of wind |
| direct current (DC) power to supply the field | | | | turbine start-up on the power system is very |
| winding, and the response of the voltage control | | | | mild, mostly because the induction machine |
| regulation mechanism. | | | | current is limited by a soft start. A soft start is a |
| Â | | | | device that limits starting current during start-up. |
| Figure 2. Diesel generator control block diagram | | | | It consists of a pair of back-to-back thyristors |
| Â | | | | installed in series with each phase of the motor |
| Â | | | | winding. Because the firing angle of the thyristor |
| B. Wind Turbine | | | | can be controlled, the size of the starting current |
| The main components of a wind turbine are the | | | | can be adjusted by controlling the firing angle of |
| rotor of the turbine, which is the prime mover, | | | | the thyristors. As we can see (Figure 5), the |
| and an induction generator. In general, the rotor is | | | | same wind turbine (225 kW) draws a starting |
| connected to the generator via a gearbox that | | | | power of 300 kW, but after the soft start is |
| matches the rotational speed. The simplest | | | | installed (Figure 7), the power surge during |
| system uses a fixed-speed turbine. A fixed-speed | | | | start-up drops to about 100 kW. After the wind |
| turbine must rely on the blade-stall condition to | | | | turbine enters generating mode (at about t = 2.5 |
| limit the output power when the winds are at high | | | | s), the local load (280 kW) is shared between the |
| speed. Note that, although the rotor speed of an | | | | diesel genset (55 kW) and the wind turbine (225 |
| induction generator varies with wind speed, the | | | | kW). The voltage and frequency are maintained |
| speed range is within a 1% to 2% slip. On the | | | | constant, and the diesel genset |
| other hand, the wind speed variation may range | | | | Â |
| from 5 m/s to 25 m/s; thus, in terms of the | | | | Â |
| wind turbine, the induction generator operates at | | | | Â |
| a relatively "fixed speed" compared to the range | | | | Figure 7. Voltage, rotor speed, and power of |
| of wind speed variation. | | | | anoversize wind turbinegenerates only a small |
| C. Induction Machines | | | | percentage of its rated load (about 13%). This |
| Most electric machines used in industry as prime | | | | makes a significant contribution to fuel savings |
| movers are induction motors. Two applications of | | | | from the wind energy. At t = 4 s, the local load is |
| induction machines in the power system network | | | | reduced from 280 kW to 100 kW; the wind |
| fall within the scope of this study: one as the | | | | speed stays the same. As a result, the wind |
| generator on a wind turbine and the other as a | | | | turbine tries to supply 225 kW, but the only load |
| motor driving large pumps and compressors. By | | | | available is 100 kW. As a result, the synchronous |
| its nature, an induction machine is an inductive | | | | generator of the diesel genset turns into a motor |
| load. This machine absorbs reactive power either | | | | (negative power), the governor loses its speed |
| as a motor or generator. The reactive power | | | | control, and frequency runaway is triggered. This |
| absorbed by the induction machine comes from | | | | is an example of the wind turbine being oversized |
| the line to which it is connected. In a hybrid power | | | | compared to the local load. In such a case, a |
| system, the reactive power comes from the | | | | dump load (water heater, water pump, battery |
| synchronous generator of the diesel genset. In a | | | | charger, etc.) is usually deployed to keep the |
| wind turbine generator, a fixed capacitor is usually | | | | diesel genset generating, which prevents it from |
| installed to supply some of the reactive power | | | | motoring. Minimum power generation of the diesel |
| that the induction generator needs. Figure 3 | | | | genset is usually pre-set (for example, 15%-40% |
| shows the equivalent circuit of an induction | | | | of the rated load). If the generated power of the |
| machine connected to a power system. The | | | | diesel genset is less than the preset value, the |
| power system is represented by infinite bus Es | | | | dump load should be deployed. The dump load |
| and the line impedance is represented by | | | | must be sized so that the diesel genset will |
| reactance Xs. | | | | always generate power above its minimum set |
| Â | | | | point. The dump loads are normally non-critical |
| Figure 3. Equivalent circuit of an induction machine | | | | loads used to store excess electrical energy in |
| connected to power system | | | | another form, such as heat (water or space |
| D. Various Loads | | | | heater), electric charge (battery charging), or |
| In the power system considered, there are two | | | | potential energy (water pump). Oversized wind |
| major loads. The first is a large water pump | | | | turbine with energy storage: As shown in the |
| representing a typical industrial load. The second is | | | | previous subsection, an oversized wind turbine can |
| a collection of loads for which the size and power | | | | drive the system into an unstable condition |
| factor can be programmed throughout the day to | | | | because of the inability of the diesel engine to |
| represent a typical village load. The voltage at the | | | | keep the frequency constant. An energy storage |
| terminal of the load varies as a result of a voltage | | | | installed in the power system network is not only |
| drop across the line impedance. The voltage drop | | | | useful to remedy the undersized diesel engine but |
| across the line impedance varies depending on the | | | | also for cases where there is an excess power |
| size of the current and the power factor of the | | | | produced by the wind turbine. Without energy |
| load. The terminal voltage for a wind turbine | | | | storage, the wind turbine can drive the |
| generator (VS), as the output current of induction | | | | synchronous machine into motoring region and the |
| machine, varies from start-up to generating mode. | | | | frequency output will be out of control. With a |
| During start-up, voltage drops significantly at the | | | | power converter to interface between the |
| terminal voltage of the induction machine. The | | | | energy storage and the power network, the |
| voltage drop across line impedance is caused by | | | | energy storage is capable of quickly absorbing |
| the current surge during start-up. In addition, the | | | | excess power generated by the wind turbine and |
| phase angle of the stator current is very large | | | | hold the generator rotor speed from a runaway |
| and lagging. The combination of a poor power | | | | condition. As shown in Figure 8, the frequency |
| factor and a lagging, large current surge creates a | | | | runaway can be prevented by using energy |
| voltage dip at the terminal of the induction | | | | storage to capture the excess power in the |
| machine during start-up. Thus, a start-up of short | | | | power network. |
| duration is preferable to a prolonged one | | | | Figure 8. Voltage, rotor speed, and power of |
| E. Energy Storage | | | | anoversize wind turbine with energy storage |
| The energy storage can be of different types (i.e. | | | | B. Case Study II: Charging the Storage Under |
| flywheel, battery, hydrogen/fuel-cell, hydropower | | | | Normal Condition |
| etc.). In this paper, we assumed energy storage | | | | The energy storage will be charged only when |
| with a power converter interface to the power | | | | there is an energy surplus from the wind and the |
| network. The power converter is connected to | | | | required network load is very light. Because the |
| the energy storage at one end. With variability of | | | | governor of the diesel generator will always |
| wind resource, energy storage is an excellent | | | | maintain the frequency constant, the output |
| contributor to the power system. The energy | | | | power of the diesel generator is an indicator of |
| storage behaves like a large buffer to | | | | the power within the system available to charge |
| accommodate the unequal instantaneous energy | | | | the energy storage. One benefit of charging the |
| in the power system. Ideally, at any instant of | | | | energy storage during this condition is that the |
| time, there should be a zero net exchange | | | | efficiency of the diesel engine is at its peak when |
| between the energy sources and the energy | | | | it is operated near its rated power. Thus, when a |
| sinks (both real and reactive power). If this | | | | surplus of power is detected within the system, |
| balance is not achieved, the voltage and | | | | the energy storage will be charged and some |
| frequency of the system changes to maintain | | | | energy will be stored within the system. The |
| equilibrium. At any instant, the energy storage | | | | amount of energy and the size of charging power |
| behaves either as an energy source or energy | | | | depend on the size of the surplus power. The |
| sink depending of the mode of operation. | | | | charging process will be stopped when the energy |
| Figure 4. Energy Storage control block diagram | | | | storage reaches its limit. Maximum charging |
| Â | | | | current is also limited by the energy storage and |
| It is assumed that the energy storage has a | | | | by the power converter interface. Figures 9 |
| power converter interfacing the power network. | | | | shows the charging process. Initially there is |
| Although it is possible for the power converter to | | | | enough wind speed to start the wind turbine. The |
| function as a reactive power compensator, the | | | | diesel generator is supplying a constant load of |
| cost of a power converter is very expensive | | | | 280 kW (power factor = 0.995 lagging) all the |
| compared to other means of reactive power | | | | time. As the wind turbine generates full power |
| compensation currently available in the market. | | | | (225kW), the diesel governor redistributes the |
| Keep in mind that the size of the power | | | | load and there is a load sharing between the wind |
| semiconductor in the power converter is limited | | | | turbine and the diesel generator. As the transient |
| by its current limit and its voltage limit. Thus, | | | | settles out, it is shown that the diesel generator is |
| minimizing the current passing through the power | | | | contributing a very small amount of power to the |
| switches will minimize the current rating of the | | | | load, thus the charging mechanism is started. The |
| power converter and will lower the cost. For this | | | | energy storage is charged slowly until it reaches |
| paper, we only used the power converter to | | | | its limit. |
| process real power in and out of the energy | | | | Â |
| storage. Figure 4 shows a block diagram of | | | | Â |
| energy storage control algorithm. It uses | | | | Figure 9. Real power flow in the power system |
| frequency deviation to indicate a real power | | | | Â |
| imbalance in the system. The frequency deviation | | | | In Figure 9, the charging of energy storage during |
| is also used as the feedback to control the | | | | normal condition is limited to 75 kW, which is |
| energy storage output. If the load power demand | | | | about 50% of the rated power of the capacitor. |
| is higher than the power supply available, the | | | | This limit ensures that the power converter still |
| frequency of the diesel generator will slowly drop. | | | | has enough headroom to deliver or absorb power |
| Other energy stored in the system includes the | | | | during an emergency. For example, if there is |
| kinetic energy in the turbine blades, the diesel | | | | some loss of the loads in the power systems, the |
| generator inertia, and energy in the inductors and | | | | energy storage must absorb the loads loss to |
| capacitors, etc. | | | | avoid a sudden change in frequency. Similarly, to |
| Â | | | | compensate for a sudden load increase to the |
| F. Balance of Energy in the System | | | | power systems (e.g. the water pump is started), |
| In the isolated system we studied, the balance of | | | | the energy storage must release energy to the |
| real and reactive power must always be | | | | power system to keep constant frequency at |
| maintained. The balance of real power is | | | | the diesel generator. As shown in Figure 9, the |
| maintained by the governor of the diesel | | | | real power used by the energy storage to |
| generator. The balance of reactive power is | | | | stabilize the frequency takes precedence over the |
| maintained by the exciter of the diesel's | | | | charging power used to charge the storage. This |
| synchronous generator. When the load demands | | | | can be seen especially when the water pump is |
| more power than the diesel and the wind turbine | | | | started at about t = 15 seconds. |
| can produce, and the diesel engine has reached its | | | | V. CONCLUSION |
| highest limit, as the loads continue to increase, the | | | | After presenting an overview of the components |
| governor of the diesel cannot push more power, | | | | of the power system under investigation, we |
| and the rotor speed of the diesel will start to | | | | described the operating characteristics of the |
| drop. The frequency of the generator will then | | | | components as they relate to voltage and |
| drop until balance is reached or the system | | | | frequency variations in the power network. The |
| collapses. The voltage in the system is also an | | | | analysis shows the dynamic interaction among the |
| indicator of the balance in the system. When the | | | | wind turbine, diesel engine, large loads, and energy |
| reactive power demand from the loads is higher | | | | storage. It also demonstrates the dynamics of |
| than what can be provided by the diesel | | | | real power balance and how the system is |
| generator, the capacitor, and other means of | | | | stabilized with the controlled energy storage. The |
| compensation, the system voltage will drop. | | | | voltage regulation is very minimal and the |
| Although the size of output and input of the | | | | frequency regulation is controlled very closely. The |
| energy storage is adjustable, it is limited by its | | | | voltage regulation is controlled mostly by the |
| ratings. For this paper, we assumed that the | | | | balance of reactive power in the system and the |
| energy storage is capable of storing and providing | | | | time constant of the excitation system of the |
| long-term energy to the power network to | | | | generator. The frequency regulation depends on |
| maintain system balance. In reality, only a limited | | | | the energy storage control, the size of the |
| amount of energy can be stored. We will not | | | | energy storage, the total inertia in the system |
| discuss energy analysis in detail in this paper. In | | | | (temporary energy storage).Many technical |
| practice, the energy will be stored when the wind | | | | solutions can be implemented to remedy the |
| turbine produces enough power and the diesel is | | | | shortcomings covered in this paper. However, as |
| operating under light load. The actual loads are | | | | in any power generation system, the economic |
| divided into critical and non-critical loads. Critical | | | | implications of the solutions must be carefully |
| loads are supplied at all times and non-critical loads | | | | considered. |
| are served only if there is enough source and it | | | | REFERENCES |
| will be shed off the system when the voltage or | | | | [1] E. Muljadi, L. Flowers, J. Green, and M. Bergey. |
| frequency drops below the allowable limit. With | | | | 1996. "Electrical Design of Wind-Electric Water |
| the existence of sufficiently sized energy storage, | | | | Pumping." ASME Journal of Solar Energy |
| it is possible to serve all the loads (critical and | | | | Engineering 118:246-252. |
| non-critical) all the time. | | | | [2] J.T.G. Pierik and M. De Bonte. 1985. Quasi |
| IV. DYNAMIC ANALYSIS | | | | Steady State Simulation of Autonomous Wind |
| The case studies look at different aspects of | | | | Diesel Systems (Status Report). Report No. |
| major power system components in the power | | | | ECN-85-091. Petten, The Netherlands: The |
| network. The first case study investigates the | | | | Netherlands Energy Research Foundation. |
| diesel power component. In the power network, a | | | | [3] A.J. Tsitsovits and L.L. Freris. 1983. Dynamics |
| diesel generator must maintain system balance by | | | | of an Isolated Power System Supplied from |
| responding properly to power changes. | | | | Diesel and Wind. Proc.IEEE 130, Part A, No. |
| A. Case Study I: Diesel-Wind Turbine Interaction | | | | 9:587-595. |
| A diesel generator consists of a diesel engine and | | | | [4] J.T. Bialasiewicz, E. Muljadi, G. Nix, and S. |
| a synchronous generator. The diesel engine is | | | | Drouilhet. 1998. "RPM-SIM Simulator: A Comparison |
| responsible for controlling the frequency and | | | | of Simulated versus Recorded Data. "Proceedings |
| keeping it constant through its governor. The | | | | of WINDPOWER '98." Bakersfield, California, |
| synchronous generator is responsible for | | | | 423-432. |
| controlling the voltage via its field winding and | | | | [5] E. Muljadi and C.P. Butterfield. 2001. |
| voltage controller. Undersized diesel engine: The | | | | "Pitch-Controlled Variable-Speed Wind Turbine |
| ability of a diesel engine to change speed is its | | | | Generation," Transactions of the IEEE-Industry |
| accelerating or decelerating power. The diesel | | | | Applications Society. |